About solenoid valve selection and common fault detection
Addtime: 2019-11-19 09:50:09   click: 857
Solenoid valve is one of the most popular industrial products. Like water pump, solenoid valve is widely used in the transportation of fluid medium. Solenoid valve product selection and common fault detection problems also need to pay attention to. The selection of solenoid valve products and common fault detection points are as follows:
 
A: solenoid valve product selection points
 
The solenoid valve was never included in the textbook of self-control, and many people thought that the selection was simple and experienced designers knew that the gadget needed to be taken seriously. Solenoid valve on its structure and principle of classification there are several, then consider a variety of technical parameters, cross combination is more. Design and purchase personnel gradually learned in the dazzling in the correct choice, in addition to collect and study sample information, but also direct consultation with manufacturing enterprises, large or important have personally inspected the economic and technical strength of the production plant and technical assurance ability, in-depth their original users, field understanding of the use of products. Now everyone has to do an accounting, but it's not just a comparison of quotes. In addition to safety, application, durability, aesthetics and other performance affect the price, but also related to the performance and cost of the whole automatic control system, piping system, this has become a comprehensive knowledge. Qipai company has a technical service department, which attaches great importance to pre-sales consulting, modeling and piping system design and other services. Design, procurement and management personnel are highly responsible and conscientious in their selection, and their dedication promotes and drives the continuous development of solenoid valve technology.
 
Solenoid valve common fault detection
 
Solenoid valve common faults 1, coil short circuit or circuit break detection
 
When we are testing the solenoid valve, its coil short circuit or break detection method is to use a multimeter to measure its on and off, resistance value tends to zero or infinite, that means the coil short circuit or break. If the measured resistance value is normal, it cannot indicate that the coil must be good, please conduct the following final test: find a small screwdriver to put in the vicinity of the metal rod in the solenoid valve coil, and then energize the solenoid valve, if you feel magnetic, then the solenoid valve coil is good, otherwise bad. Treatment: replace the solenoid valve coil.
 
Solenoid valve common faults 2, plug/socket problems
 
Failure: if the solenoid valve is a plug/socket type, there may be a problem with the metal spring of the socket, a problem with the wiring of the plug, etc. The power cannot be sent to the coil.
 
Make it a good habit to turn on the fixing screw after the plug is in the socket and the fixing nut after the spool stem on the coil. If the plug of solenoid valve coil is equipped with led power indicator light, then when using DC power to drive the solenoid valve, it should be connected, otherwise the indicator light will not be on. In addition, do not replace power plugs with led power indication of different voltage levels, which may cause the led to burn out/the power to short circuit or the led to emit very weak light.
 
If there is no power indicator, the solenoid coil does not have to distinguish polarity.
 
Solenoid valve common faults 3: wiring error, repair or replace the plug, socket, valve core problem
 
Fault phenomenon 1: in the solenoid valve by the media pressure normal, press the solenoid valve red manual button, solenoid valve is not responsive, that the valve core must be bad. Treatment method: check whether there is a problem with the medium, such as whether there is a lot of water in the compressed air, whether there are a lot of impurities in the liquid medium. Then remove solenoid valve and pipeline water or impurities. If not, please repair or replace the spool, or simply replace the entire solenoid valve.
 
2: after inspection, the coil is the original coil and the coil is energized when the magnetic normal, but the solenoid valve is still not action, that the valve core is bad. Treatment: please repair or replace the spool, or simply replace the entire solenoid valve.